Omron CJ2 User Manual Page 17

  • Download
  • Add to my manuals
  • Print
  • Page
    / 40
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 16
17
System Configuration
CJ-series Expansion Racks
A CJ-series Expansion Rack consists of a Power Supply Unit, an I/O Interface Unit, Configuration Units (Basic I/O Units, Special I/O
Units, and CPU Bus Units), and an End Cover.
Configuration Units: 10 max.
Power Supply Unit
CJ1W-P@@@(@)
CPU Unit
CJ2H-CPU@@-EIIP
I/O Control Unit
CJ1W-IC101
I/O Interface Unit
CJ1W-II101
Power Supply Unit
CJ1W-P@@@(@)
Power Supply Unit
CJ1W-P@@@(@)
Power Supply Unit
CJ1W-P@@@(@)
CPU Rack
Expansion
Rack
Expansion
Rack
Number of Expansion Racks:
Up to 3 Expansion Racks can be connected.
I/O Connecting Cable
CS1W-CN@@3
Configuration Units: 10 max.
I/O Interface Unit
CJ1W-II101
I/O Interface Unit
CJ1W-II101
I/O Connecting Cable
CS1W-CN@@3
I/O Connecting Cable
CS1W-CN@@3
Expansion
Rack
Total
cable
length
12 m
Configuration Units: 10 max.
Configuration Units: 10 max.
Required Units
Rack Unit name Required number of Units
CPU Rack I/O Control Unit
One Unit. Required only when an Expansion Rack is used. Mount the I/O Control Unit immediately to the
right of the CPU Unit. (See note 1.)
Expansion
Rack
Power Supply Unit
One Unit
I/O Interface Unit
One Unit. Mount the I/O Interface Unit immediately to the right of the Power Supply Unit. (See note 2.)
Number of Configuration Units
Ten Units max. (The number of Basic I/O Units, Special I/O Units, and CPU Bus Units can be varied.
This number does not include the I/O Interface Unit.)
End Cover
One (Included with the I/O Interface Unit.)
Note: 1. Mounting the I/O Control Unit in any other location may cause faulty operation.
2. Mounting the I/O Interface Unit in any other location may cause faulty operation.
Maximum Number of Configuration Units That Can Be Mounted
CPU Unit Model Total Units No. of Units on CPU Rack No. of Expansion Racks
CJ2H CJ2H-CPU68-EIP
40 10 per Rack 3 Racks x 10 Units
CJ2H-CPU67-EIP
CJ2H-CPU66-EIP
CJ2H-CPU65-EIP
CJ2H-CPU64-EIP
Page view 16