Parameters Status Data, Message (Response)
“Status data” consists of four digits (two bytes) hexadecimal. The leftmost byte
indicates CPU operation mode, and the rightmost byte indicates the size of the
program area.
15
14 13 12 11 10 9 8
00 0
98
00
10
1
1
x 16
3
x 16
2
This area is different
from that of
STATUS WRITE.
Bit
Bit
1: FALS generated
1: Fatal error generated
Operation mode
PROGRAM mode
RUN mode
MONITOR mode
1: Remote I/O
waiting for power
application
76543210
1 000
x 16
1
x 16
0
65
10
4
0
Bit
Bit
32 Kbytes
Program area write enable
0: Disabled (DIP switch pin 1 is ON)
1: Enabled (DIP switch pin 1 is OFF)
Program area
“Message” indicates the FAL/FALS number generated at the point when the
command is executed. When there is no message, this is omitted.
11-3-22 STATUS WRITE –– SC
Changes the PC operating mode.
Command Format
@ SC
x 10
0
x 10
1
x 16
1
x 16
0
:
Node no. Header
code
TerminatorFCS
Mode data
Response Format
@ SC
x 10
0
x 10
1
x 16
1
x 16
0
:
TerminatorFCS
Node no. Header
code
End code